INTRODUCTION OF FIRE PROTECTION SYSTEM

 

INTRODUCTION OF FIRE PROTECTION SYSTEM

 

The Fire Hydrant System unlike the Portable (First – Aid) Fire Extinguishers basically uses water as extinguishing media.

 

 A raging fire without a proper extinguishing system can be devastating. Hence there is an emphasis on provision of a Fire Hydrant System.

 

In the Fire Hydrant System, the Water in large quantum is pumped continuously with tremendous force and velocity so as to reach the seat of fire. Hydrant valves are located at strategic points. These are work as outlets of water through the Fire Hose.

 

1.1       Automatic Fire Hydrant System

 

In the case of the Automatic Fire Hydrant system the piping network is pressurized with water at a definite pressure and is maintained in readiness for any eventuality. Once the Hydrant valve is manually opened during fire, the fall in pressure in the pipe line is sensed by the pressure switches activating the pumps, thereby ensuring continuous supply of water and pressure at the outlets (Hydrant Points)

 

1.2            Water for Fire Fighting

 

Generally, the water is stored in underground sumps, underground Water Tanks or Overhead reservoirs. The capacity of these tanks can be derived based on the nature of Buildings and Hazard i.e., Ordinary; Light; Medium & High Hazard Occupancies as per TAC.

 

1.3       Pumping Facility

 

The Pumping facility may consist of multiple pumps at centralized locations, close to and drawing water from the Fire fighting reservoir. These pumps are driven with suitable prime movers at required speed to pump the required quantity of water from the reservoir in to the piping system and finally out of the Hydrants, to fight the fire.

 

The pumps are located in level with the floor of the Tank sump or reservoir, so that a flooded suction is achieved, which is called the positive suction, or it can be placed above the top level of the water and the pump sucks the water. This scheme is called the negative suction of the pump. Pumps can be selected to throw water at required velocities, the required quantities at the required sequence – on occurrence of fire.

 

The main pump is generally provided with a standby pump of same capacity to cater to a break down during fire.

 

In our case it is positive suction pump and it consist by one Jockey pump for maintaining the line pressure, main pump for sprinkler & Hydrant System & Diesel engine operated pump as standby pump.  

 

1.4       Piping Network

 

The piping network runs partly underground and partly over ground but, finally emerges out of ground at various points of utility.  The network of piping carries water from the point it is pumped into, till the hydrant and is designed to cater to the pressure within the pipes.

 

1.5            Hydrants Points

 

Hydrants are generally seen in close vicinity of the protected buildings. These are painted red in color for easy identification. The stand post of the hydrant is an 80 NB dia pipe projecting out of ground and fixed with a Hydrant valve with an outlet hand wheel for operating the valve.  Hydrants also consist of a glass - fronted cabinet housing hoses and branch pipe with nozzle to direct the water to the base of fire.

 

Hydrant points are located at required span between each other, at strategic points so as to be able to combat the fire from all sides. Near each hydrant point, a hose box is provided with a set of fire hoses & branch pipe with nozzle to direct the water to the base of fire.

 

Hydrants and its components are designed keeping in mind that no time is wasted from the time the fire is detected and the fire fighting commences.

 

2.0    INTRODUCTION ABOUT FIRE ALARM AND DETECTION SYSTEM

 

2.1       System Description

 

General: Provide a complete, , [addressable],  Microprocessor-based fire alarm system with [initiating devices], [notification appliances,] [and] monitoring and Control devices] as indicated on the drawings.

 

Software: The fire alarm system shall allow for loading and editing instructions and operating sequences as necessary. The system shall be capable of storing, and downloading while the system is in operation, a second set of operating software resident in the control panels as backup in case primary operating software is corrupted.

 

In addition, the system shall be capable of on-site programming to accommodate system expansion and facilitate changes in operation. All software operations shall be stored in a non-volatile programmable memory within the fire alarm control unit. Loss of primary and secondary power shall not erase the instructions stored in memory.

 

History Logs: The system shall provide a means to recall alarms and trouble conditions in chronological order for the purpose of recreating an event history. A separate alarm and trouble log shall be provided.

 Reference

 

Conventional Operation. Each addressable device on the communication channel is continuously interrogated for status condition such as: normal, off-normal, alarm, supervisory, or trouble. Sophisticated poll and response communication techniques ensure supervision integrity operation. The device LED blinks to indicate. Receipt of a communications poll and is steady on to indicate an alarm (or trouble) condition.

 

CPU bay system power supply (SPS) provides an IDNet signaling line circuit (SLC) that supports up to a considerable / OEO specified addressable monitor and control points intermixed on the same pair of wires.


Post a Comment

Previous Post Next Post